IP CLASSIFICATIONS

NEMA / UL  CLASSIFICATIONS

Ingress protection class of enclosures is according to IEC 529 given in form of IP classification, a two digit coding which is shown below NEMA performance criteria and test methods are used by Underwriters Laboratories as guidelines for investigation and listing of electrical enclosures.

First Digit

Second digit  
Protection against contact and ingress of solid objects Protection against ingress of water Approx. IP equivalents in red.
0 No special protection 0 No special protection 1

 

IP30

Indoor use primarily to provide a degree of protection against contact with the enclosure equipment and against a limited amount of  falling dirt
1 Protected against ingress solid objects with a diameter of more than 50 mm. No protection against deliberate access, e.g. with a hand, but large surfaces of the body are prevented from approach 1 Protection against dripping water falling vertically. No harmful effect must be produced (vertically falling drops) 2

 

IP31

Indoor use to provide a degree of protection against limited amounts of falling water and dirt
2 Protected against penetration by solid objects with a diameter of more than 12 mm. Fingers or similar objects prevented from approach 2 Protection against dripping water falling vertically. There must be no harmful effect when the equipment (enclosure) is tilted at an angle up to 15° from its normal position (drops falling at an angle). 3

 

IP64

Outdoor use to provide a degree of protection against windblown dust, rain and sleet; undamaged by the formation of ice on the enclosure
3 Protected against ingress of solid objects with a diameter of more than 2.5 mm. Tools, wires etc. with a thickness of more than 2.5 mm are prevented from approach 3 Protection against water falling at any angle up to 60° from the vertical. There must be no harmful effect (spray water). 3R

 

IP32

Outdoor use to provide a degree of protection against rain and sleet:; undamaged by the formation of ice on the enclosure
4 Protected against ingress of solid objects with a diameter of more than 1 mm. Tools, wires etc. with a thickness of more than 1 mm are prevented from approach 4 Protection against water splashed against the equipment (enclosure) from any direction. There must be no harmful effect (splashing water). 4 (X)

 

IP66

Indoor or outdoor use to provide a degree of protection against splashing water, windblown dust and rain, hose directed water; undamaged by the formation of ice on the enclosure. (Resist corrosion).
5 Protected against harmful dust deposits. Ingress of dust is not totally prevented but the dust must not enter in sufficient quantity to interface with satisfactory operation of the equipment. Complete protection against contact. 5 Protection against water projected from a nozzle against the equipment (enclosure) from any direction. There must be no harmful effect (water jet). 12/12K

 

IP65

Indoor use to provide a degree of protection against dust, falling dirt and dripping non corrosive liquids.
6 Protection against ingress of dust (dust tight). Complete protection against contact. 6 Protection against heavy seas or powerful water jets. Water must not enter the equipment (enclosure) in harmful quantities (splashing over). 13

 

IP65

Indoor use to provide a degree of protection against dust and spraying of water, oil and non corrosive coolants.
    7 Protection against water when the equipment (enclosure) is immersed in water under defined conditions of pressure and time. Water must not enter in harmful quantities (immersion)    
    8 The equipment (enclosure) is suitable for continuous submersion in water under conditions which must be specified by the manufacturer (submersion).    

  Download Printable Copy

 

Phone: +1-215-340-2650
Fax:    
+1-215-340-3670
 

Home  ·   About us  ·   Privacy  ·   Terms  ·   Contact  ·   Links  ·   UPS  ·   Engineering information  ·   News and updates  ·   Industrial humidity transmitters  ·   HVAC humidity transmitters  ·   Humidity sensors and OEM configurations  ·   Additional humidity instrumentation  ·   Inline dewpoint meters  ·   Dewpoint transmitters  ·   Portable dewpoint meters  ·   Carbon dioxide transmitters  ·   Air velocity instrumentation  ·   Handheld instrumentation  ·   Low and extreme low flowmeters  ·   High viscosity oval gear flowmeters  ·   Gas and liquid turbine flowmeters  ·   Ultrasonic flowmeters  ·   Beverage flowmeters for wine, beer and spirits  ·   Inline Atrato  ·   Handheld meters for RH, T and AV  ·   Air Velocity / Temperature Transmitters